BC Energy Step Code levels: what Steps 3, 4 and 5 require, and what each Metro Vancouver city asks for

The BC Energy Step Code is the part of the BC Building Code that sets energy targets for new buildings in numbered steps, where a higher step means a building that needs less energy. For houses and small residential buildings, Steps 1 and 2 are now Reserved, so Step 3 is the lowest step a new home can use. Each step sets three limits: how much heat the building may need in a year, how much energy its heating, cooling, fan and hot water equipment may use, and how much air may leak through its shell. A separate Zero Carbon Step Code sets four emission levels, EL-1 to EL-4. Cities may require higher steps and levels by bylaw, and in Metro Vancouver Burnaby, Richmond, New Westminster and the City of North Vancouver do.

Part of Energy-efficient homes in BC: the Step Code, testing, and heating. Figures re-verified 2026-10-24.

Key takeaways

  • Steps 1 and 2 for smaller buildings are listed as Reserved in the BC Building Code, so a new house starts at Step 3.
  • In places with fewer than 3,000 heating degree-days, such as Vancouver and Burnaby, Steps 3, 4 and 5 allow 30, 20 and 15 kWh per square metre per year of heating demand.
  • Air leakage limits are 2.5, 1.5 and 1.0 air changes per hour at 50 pascals for Steps 3, 4 and 5.
  • Since 10 March 2025 the province requires most new buildings to meet at least EL-1 of the Zero Carbon Step Code.
  • Burnaby requires Step 3 with EL-4 for new Part 9 homes with permits submitted on or after 1 January 2025.
  • In a building with more than one home, such as a fourplex, the Step Code applies to the whole building.

Three limits in every step

The Step Code applies to houses and to small buildings that hold only homes. Note A-9.36.1.3.(3) of the BC Building Code lists what counts as a house for this purpose: detached houses, semi-detached houses, duplexes, triplexes, townhouses, row houses and boarding houses. Sentence 9.36.1.3.(3) says these buildings, and buildings holding only homes with common space of no more than 20 percent of the floor area, comply through Subsection 9.36.6, which is the Step Code.

Each step in Tables 9.36.6.3.-A to -F sets three limits. The first is thermal energy demand intensity, shortened to TEDI. Article 9.36.6.2 defines it as the yearly heat the building needs for its rooms and for warming fresh air, per square metre of conditioned floor space. It looks at the walls, roof, floors, windows, air leakage, heat from people and equipment, and heat recovered from exhaust air. TEDI measures the shell, whatever the heating equipment.

The second limit is mechanical energy use intensity, shortened to MEUI. It is the yearly energy used by the heating, cooling, fan, hot water, pump and other heating and ventilation equipment, per square metre. Table 9.36.6.3.-H sets it by floor area, by climate and by whether more than half the home is cooled. A small home gets a larger allowance per square metre than a large one.

The third limit is airtightness, set as an Airtightness Level. Table 9.36.7.4 gives AL-1 a limit of 2.5 air changes per hour at 50 pascals of test pressure, AL-3 a limit of 1.5, and AL-4 a limit of 1.0. Step 3 uses AL-1, Step 4 uses AL-3 and Step 5 uses AL-4. The testing chapter of this guide explains the test.

StepHeating demand limit (TEDI)Airtightness levelAir leakage limit (ACH50)Equipment energy limit
1ReservedReservedReservedReserved
2ReservedReservedReservedReserved
330 kWh/(m²·year)AL-12.5Table 9.36.6.3.-H by floor area
420 kWh/(m²·year)AL-31.5Table 9.36.6.3.-H by floor area
515 kWh/(m²·year)AL-41.0Table 9.36.6.3.-H by floor area
Step Code limits for buildings where the degree-days below 18°C are under 3,000 (BC Building Code 2024, Table 9.36.6.3.-A and Table 9.36.7.4)

Why the same step means different numbers in Vancouver and Vernon

The tables are sorted by climate, measured in heating degree-days below 18°C, which is a count of how cold a place is over a year. Table C-2 in Appendix C of the BC Building Code lists the value for each location. Vancouver City Hall is 2,825, Burnaby (general) 2,735, Surrey at 88 Avenue and 156 Street 2,750, Richmond 2,800, New Westminster 2,800 and North Vancouver 2,910. All of these are under 3,000, so Table 9.36.6.3.-A applies.

Vernon is listed at 3,600 degree-days, which puts it in Table 9.36.6.3.-B. There the heating demand limits are 40, 30 and 20 kWh per square metre per year for Steps 3, 4 and 5. The airtightness levels stay the same. A colder place gets a larger heating allowance because a house there needs more heat to stay at the same indoor temperature.

Sentence 9.36.6.3.(4) adds a formula that adjusts the heating limit for the actual degree-days of the site. It moves the limit part of the way toward the next table as the site gets colder. Your energy advisor applies it in the model.

There is a second route. Table 9.36.6.3.-G lets a building show a percent improvement against a reference house built to the code's base rules, plus a percent cut in heat loss. For a building over 300 cubic metres, Step 3 needs at least a 20 percent improvement and a 10 percent heat loss cut, Step 4 needs 40 and 20 percent, and Step 5 needs 70 and 40 percent. The same airtightness levels apply.

The Zero Carbon Step Code levels

The Zero Carbon Step Code was added to the code in May 2023. It limits greenhouse gas emissions from the energy a building uses, mostly from heating and hot water. The province names the four levels Measure-only (EL-1), Moderate Carbon Performance (EL-2), Strong Carbon Performance (EL-3) and Zero Carbon Performance (EL-4). Starting 10 March 2025, the province requires most new buildings to meet or exceed EL-1. Local governments can require any level.

Table 9.37.1.3 gives each level three ways to comply. One is a yearly cap on total emissions for the house. One is an emissions intensity cap per square metre paired with a total cap. The third is a rule about fuel: the energy sources for named systems must have an emissions factor of 0.011 kg of carbon dioxide equivalent per kWh or less. Sentence 9.37.1.3.(2) sets electricity at 0.011 and natural gas at 0.180, so on this third route only electricity qualifies.

The province's page describes a prescriptive path for Part 9 buildings, which asks builders to use lower-carbon equipment for space heating, water heating and cooking, with more of it at higher levels. It also describes a performance path with an emissions target, where energy advisors can show whether other gas equipment, such as a fireplace, cooktop or clothes dryer, still fits.

LevelTotal emissions cap per houseOr intensity cap with total capOr energy sources at 0.011 kgCO2e/kWh or less for
EL-1Measure onlyMeasure onlyNot applicable
EL-21,050 kgCO2e/year6.0 kgCO2e/m²/year and 2,400 kgCO2e/yearHeating systems
EL-3440 kgCO2e/year2.5 kgCO2e/m²/year and 800 kgCO2e/yearHeating and service water heating systems
EL-4265 kgCO2e/year1.5 kgCO2e/m²/year and 500 kgCO2e/yearAll building systems, including equipment and appliances
Zero Carbon Step Code levels (BC Building Code 2024, Table 9.37.1.3)

What each Metro Vancouver city asks for

The province's requirements page says Step Code requirements depend on the building permit date and the location, and that local governments may require higher steps through bylaw. The table below lists the rule for new Part 9 homes in each city whose own page we read on 24 October 2026. Part 9 means buildings of 3 storeys or less with a footprint of 600 square metres or less, which, as Surrey's page explains, covers houses, duplexes, townhomes and small apartment buildings.

Two cities are missing. The City of Vancouver does not use the BC Building Code; the province's code page says Vancouver has its own building bylaw. Vancouver's web pages refused our requests on 24 October 2026, so we state no Vancouver rule here. Ask the City for the energy and emission rules that apply to your permit date. We also could not open the District of North Vancouver's page.

Cities change these rules often. New Westminster's published timeline already lists a further rise on 1 January 2027, and Richmond lists a different rule for permits submitted before 31 October 2023. Confirm the rule with the city on the day you apply, because the permit date decides which rule applies.

For a building with more than one home, the city's step applies to the whole building. Sentence 9.36.6.1.(1) says that where a building has more than one dwelling unit, the Step Code applies to the energy performance of the building and not to each unit, and Sentence 9.37.1.1.(2) says the same for emissions. A fourplex is modelled and tested as one building.

CityEnergy Step CodeZero Carbon Step CodeApplies to
BurnabyStep 3EL-4New Part 9 residential buildings, permits submitted on or after 1 January 2025
RichmondStep 5, or Step 4, or Step 3EL-2 with Step 5, EL-3 with Step 4, EL-4 with Step 3Part 9 residential, permits submitted on or after 31 October 2023
New WestminsterStep 5, or Step 4EL-2 with Step 5, EL-4 with Step 4Part 9 buildings, permits filed on or after 1 January 2025; timeline lists Step 5 with EL-4 from 1 January 2027
City of North VancouverStep 4, or Step 5EL-3 with Step 4, EL-1 with Step 5New residential buildings, applications from 1 November 2023
SurreyStep 3EL-1Part 9 houses, duplexes, houseplexes, townhouses and small apartments
CoquitlamStep 3No level listed on the City's page; the provincial minimum is EL-1Part 9 small residential, from 1 January 2024
Step Code rules for new Part 9 homes, from each city's own page, read 24 October 2026

Frequently asked questions

What does thermal energy demand intensity mean?

It is the yearly heat a building needs for its rooms and for warming fresh air, divided by its conditioned floor area, in kWh per square metre per year. Article 9.36.6.2 of the BC Building Code defines it and lists what it counts: walls, roof, floors, windows, air leakage, internal heat gains and heat recovered from exhaust air. A lower number means a tighter, better-insulated shell.

What is mechanical energy use intensity in the Step Code?

It is the yearly energy used by a building's heating, cooling, fan, hot water, pump and other heating and ventilation equipment, per square metre of conditioned floor area. Table 9.36.6.3.-H sets the limit by step, climate, floor area and how much of the home is cooled. Smaller homes get a higher limit per square metre.

Which Step Code table applies to a home in Vancouver or Burnaby?

Table 9.36.6.3.-A, for places with fewer than 3,000 heating degree-days. Table C-2 of the BC Building Code lists Vancouver City Hall at 2,825 and Burnaby (general) at 2,735. Note that the City of Vancouver uses its own building bylaw, so check its rules with the City.

What Step Code heating limit applies to a new house in Vernon?

Table C-2 of the BC Building Code lists Vernon at 3,600 heating degree-days, so Table 9.36.6.3.-B applies. Its heating demand limits are 40, 30 and 20 kWh per square metre per year for Steps 3, 4 and 5. Step 3 is the provincial minimum; ask the City of Vernon whether it requires a higher step.

How airtight must a house be at each Step Code step?

Step 3 uses Airtightness Level AL-1, which allows 2.5 air changes per hour at 50 pascals. Step 4 uses AL-3 at 1.5, and Step 5 uses AL-4 at 1.0. Table 9.36.7.4 of the BC Building Code also gives the same levels in two other test measures, leakage area and leakage rate.

What is the percent improvement route in the Step Code?

It is a second way to meet a step, set out in Table 9.36.6.3.-G. The energy model compares the design with a reference house built to the code's base rules. For a building over 300 cubic metres, Step 3 needs a 20 percent improvement and a 10 percent cut in heat loss, and Step 5 needs 70 and 40 percent.

What do the levels EL-1 to EL-4 mean in the Zero Carbon Step Code?

They are four emission levels. EL-1 asks only that emissions be measured and reported. EL-2, EL-3 and EL-4 set lower and lower caps, or require electric heating, then electric heating and hot water, then electric supply for all building systems. Table 9.37.1.3 of the BC Building Code sets the numbers.

What energy and carbon steps does Burnaby require for new homes in 2026?

Step 3 of the Energy Step Code and EL-4 of the Zero Carbon Step Code, for new Part 9 residential buildings with permits submitted on or after 1 January 2025. Burnaby's page says gas cooktops are not allowed at EL-4 on the prescriptive path. Burnaby's rules sit in Section 9B of its Building Bylaw.

Why does Richmond list three Step Code options?

Richmond pairs a higher energy step with a lower carbon level, or a lower step with a higher level. For Part 9 residential permits submitted on or after 31 October 2023, a builder may choose Step 5 with EL-2, Step 4 with EL-3, or Step 3 with EL-4. The choice changes how much the shell must do and how much the heating fuel must do.

What will New Westminster require for new homes from January 2027?

New Westminster's published timeline lists Step 5 of the Energy Step Code with EL-4 of the Zero Carbon Step Code for Part 9 homes from 1 January 2027. Until then, Part 9 buildings with permits filed on or after 1 January 2025 may use Step 5 with EL-2 or Step 4 with EL-4. Confirm the rule with the City before you apply.

Does a fourplex meet the Step Code as one building or as four homes?

As one building. Sentence 9.36.6.1.(1) of the BC Building Code says that where a building has more than one dwelling unit, the Step Code applies to the building and not to each unit. Sentence 9.37.1.1.(2) applies the same rule to emissions. The energy advisor models and tests the whole building.

Go deeper in the Journal

Sources and references

Rate and regulation figures on this page were re-verified on 2026-10-24. Construction cost ranges come from Venture Pacific's own Metro Vancouver projects and are described as such wherever they appear.

  1. British Columbia Building Code 2024, Book I (General), Revision 2: Division B, Sections 9.32, 9.33, 9.36 and 9.37, and Appendix C, Table C-2Province of British Columbia. Code in effect 8 March 2024. Accessed 24 October 2026.
  2. BC Energy Step CodeProvince of British Columbia. Page last updated 9 June 2025. Accessed 24 October 2026.
  3. Zero Carbon Step CodeProvince of British Columbia. Page last updated 9 June 2025. Accessed 24 October 2026.
  4. BC Energy and Zero Carbon Step Code requirementsProvince of British Columbia. Page last updated 28 July 2025. Accessed 24 October 2026.
  5. BC Building Code 2024Province of British Columbia. Publication date 10 March 2025. Accessed 24 October 2026.
  6. Green building and land development: Energy Step Code and Zero Carbon Step Code requirementsCity of Burnaby. Accessed 24 October 2026.
  7. Better Buildings: Energy and Zero Carbon Step Codes in RichmondCity of Richmond. Accessed 24 October 2026.
  8. Buildings and Climate Action: BC Energy and Zero Carbon Step CodesCity of New Westminster. Accessed 24 October 2026.
  9. BC Energy Step Code for New Buildings: Requirements for Part 9 BuildingsCity of North Vancouver. Accessed 24 October 2026.
  10. BC Energy Step Code and Zero Carbon Step CodeCity of Surrey. Page modified 22 October 2026. Accessed 24 October 2026.
  11. Energy Step CodeCity of Coquitlam. Accessed 24 October 2026.